High performance and ultra-HEPA – disposable filter cage (HEPA/ULPA)
FEATURES
The disposable box set is designed for the dry ceiling skeleton of the clean room, and the designer can configure the usage to meet the specifications and operating costs.
Based on the number of filters used in the ceiling, the air circulation rate and the overall clean room design, this laminar flow filter can provide cleanliness standards ranging from 1 to 100,000.
- Disposable HEPA high efficiency filter cage
Efficiency: PAO 99.99%, 99.995% at 0.3µm
Standard: EN1822, Class H13 / H14. - Disposable ULPA ultra high efficiency filter cage
Efficiency: PAO 99.9995%, 99.99995% at 0.12µm
Standard: EN1822, Class U15 / U16 - The size of the air inlet is 14″, 12″, 10″, 8″ to choose from.
- A large-volume air filter is also available.
- Provide a variety of configurations to meet various strict clean requirements.
※ The filter screen can be flexibly designed according to customer needs, and the material, origami thickness, filter efficiency, air volume and air inlet size can be selected.
※ Various sizes, specifications and any special functions can be customized.
※ All kinds of special customized designs, there are too many types to be uploaded, please inquire and refer to the actual performance unit.
Specification
Material, conditions of use
Frame | Aluminum (Etruded Anodized) |
filter Media |
Waterproof fire retardant glassfiber |
Faceguard | Aluminum (Etruded Anodized) |
Gasket | Neoprene EPDM |
Bond | Epoxy Resin PU Fire-retadant Urthane |
Temperature | 80°C |
Humidity% RH | 100% (No condensation state) |
Test conditions
Test Method |
|
Efficiency HEPA | ≥ 99.97%, ≥ 99.99% (0.3µm) |
Efficiency ULPA | ≥ 99.999%, ≥ 99.9995% (0.1µm-0.2µm) |
HEPA air volume and size table (size mark: HxWxD mm) does not include the height of the air inlet
Model | Efficiency (%) |
Rated Capacticy (m3/min) | Actual size HxWxDmm |
Type | INITIAL P.D | FINAL P.D |
HAC (HEPA) |
99.97 99.99 |
14.9CMM (526CFM) | 570x570x150 | T-Bar type | 25.4 mmH2O (250 Pa) |
50.4 mmH2O (500 Pa) *Recommended value |
31.4CMM (1109CFM) | 570x1170x150 | |||||
16.6CMM (586CFM) | 600x600x150 | Light steel frame type | ||||
34.3CMM (1211CFM) | 600x1210x150 | |||||
17.2CMM (607CFM) | 610x610x150 | Library board type | ||||
35.2CMM (1243CFM) | 610x1220x150 |
ULPA air volume and size table (size mark: HxWxD mm) does not include the height of the air inlet
Model | Efficiency (%) |
Rated Capacticy (m3/min) | Actual size HxWxDmm |
Type | INITIAL P.D | FINAL P.D |
UAC (ULPA) |
99.999 99.9995 |
8.7CMM (307CFM) | 570x570x150 | T-Bar type | 27.5 mmH2O (275 Pa) |
50.4 mmH2O (500 Pa) *Recommended value |
18.5CMM (635CFM) | 570x1170x150 | |||||
9.7CMM (343CFM) | 600x600x150 | Light steel frame type | ||||
20.2CMM (713CFM) | 600x1210x150 | |||||
10.1CMM (357CFM) | 610x610x150 | Library board type | ||||
20.7CMM (731CFM) | 610x1220x150 |